CROSS CONNECTION RULES AND REGULATIONS
HALLOWELL WATER DISTRICT


I .    Purpose
             Cross-connections between water supplies and non-potable sources of contamination represent one of the most significant threats to health in the water supply industry. This program is therefore designed to maintain the safety and potability of the water in the supplier's system by preventing the introduction of any foreign liquids, gases or other substances, other than water from the intended source.

II.    Authority
              This program derives its enforce ability from Title 22, MRSA, C 601, sub-chapter 2, Sec. 2612(5) Maine Department of Human Services, Cross- Connection Rules 10-144ACMR226. In addition, authority rises from the Rules and Regulations as published by the Hallowell Water District and as approved by the Public Utilities Commission of the State of Maine and from provisions of the Occupational Safety and Health Act, and from provisions of the State Plumbing Code Part 0 10-144A CMR 238.

III. Definitions
            A.     Backflow The flow of water or other foreign liquids gases or other substances into the distribution system
                    of a public water supply from any source other than the intended

            B.     Backflow Preventer "A device to prevent backflow "
                        1.     Air Gap A physical separation sufficient to prevent backflow between the free-flowing discharge end
                                of the potable water system and any other system.
                        2.     Atmospheric Vacuum Breaker A device which prevents back-siphonage by creating an atmospheric
                                vent where there is either a negative pressure or sub-atmospheric pressure in a water system.
                        3.     Backflow Preventer with Intermediate Atmospheric Vent A device having two check valves separated
                                by an atmospheric vent.
                        4.     Double Check Valve A device having two, weight or spring loaded, bronze faced with soft rubber
                                disc check valves, with shutoff valves and test cocks for periodic testing.
                        5.     Hose Bibb Vacuum Breaker A device which is permanently attached to a hose bibb and which acts as
                                an atmospheric vacuum breaker.
                        6.     Pressure Vacuum Breaker A device containing a spring loaded check valve and a spring loaded
                                atmospheric vent. which opens when pressure approaches atmospheric. It contains valves and fittings
                                which allow the device to be tested.
                        7.     Reduced Pressure Principle Backflow Preventer An assembly of check valves and a reduced pressure
                                zone which spills water to the atmosphere In event of the failure of the check valves. It has valves and
                                fittings which allow the device to be tested.

            C.     Back-siphonage Backflow resulting from negative or less than atmospheric pressure in the water system.

            D.     Back-pressure A condition in which the owner's system pressure is greater than the supplier's system pressure.

            E.     Containment A method of backflow prevention which requires a backflow preventer at the water service
                    entrance.

            F.     Cross-connection Any physical connection or arrangement between two otherwise separate piping systems, one
                    of which contains potable water and the other water or other substances of unknown or questionable safety,
                    whereby water or other substances may flow from one system to the other, the direction of flow depending on
                    the pressure differential between the two systems.

            G.     Department State of Maine Department of Human Services.

            H.     Fixture Isolation A method of backflow prevention in which a backflow preventer is located to correct a
                    cross-connection at an in-plant unit rather than at the water service entrance.

            I.     Owner Any person who has a legal title to, or license to operate or habitats in, a property upon which a
                    cross-connection inspection is to be made or upon which a cross-connection is present. J. Permit A document
                    issued by the Department with the approval of the supplier which requires the use of a backflow preventer.

            K.     Person Any individual, partnership, company, public or private corporation, political subdivision or agency of the
                    State, department, agency or instrumentality of the United States or any other legal entity.

            L.     Supplier Hallowell Water District or any person who controls, owns, or generally manages a system of pipes,
                    structures and facilities through which water is delivered for human consumption.

            M.     Water Service Entrance That point in the owner's water system beyond the sanitary control of the supplier. This
                      will ordinarily be the outlet end of the meter and will always be before any unprotected branch.

IV.     Administration
            A.     The Supplier shall develop and operate a cross -connection control program, Including keeping necessary
                     records, which fulfills the requirements of the Department's Cross-Connection Rules and is approved by the
                     Department.

            B.     The Owner shall allow his property to be inspected for possible cross-connections and shall follow the provisions
                    of the Supplier's program or the Department's Cross- Connection Rules if a cross-connection is permitted.

            C.     If the Supplier requires that the public supply be protected by containment, the Owner shall be responsible for
                    water quality beyond the outlet end of the containment device.

            D.     Both the Supplier and the Owner shall attempt to eliminate all cross-connections.

V.     Responsibility
            A.     Supplier's Responsibility

                        1.     The Supplier's inspections for cross- connections or potential cross -connections shall be made during
                                normal working hours unless otherwise arranged with the owner.

                        2.     The Supplier will, after the initial inspection of plans or premises, inform the owner by letter of any
                                correction deemed necessary, the method of making the correction, and a maximum of thirty (30) days to
                                make the correction.

                        3.     The Supplier will not allow any cross-connection to remain unless it is protected by an approved
                                backflow preventer, for which a permit has been issued and which is regularly tested and operates
                                satisfactorily. Certain fixtures are exempted from this provision and are listed in Section VIII.

                        4.     The Supplier shall inform the Owner by letter of any failure to comply by the time of the first
                                 re-inspection.
                                The Supplier will allow fifteen (15) additional days for the correction If there is a failure to comply by the
                                time of the second re-inspection, the Supplier shall inform the Owner by letter that water service to the
                                Owner's premises will be terminated. The termination procedure shall be that specified in the Supplier's
                                rules and regulations for non-payment.

                        5.     If the Supplier determines at any time that a serious threat to the public health exists, service shall be
                                terminated immediately.

                        6.     Re-establishment of service before the installation of a backflow preventer may be allowed by the
                                Supplier after an agreement has been made between the Supplier, the Department and the Owner
                                indicating the intention of the Owner to comply with the provisions of the agreement.

                        7.     The Supplier shall maintain an inspection program which covers all industrial customers every three years
                                and all commercial customers every five years.

                        8.     The Supplier will make sure that new water service areas and all new construction, including residential,
                                complies with the Cross- Connection Program and with the Maine State Plumbing Code. A copy of the
                                Plumbing Inspector's Certificate of Completion should be obtained by the Supplier.

                        9.     The Supplier shall inspect dwellings with more that four apartments and require that they comply with the
                                Cross-Connection Program.

                        10.   The Supplier should encourage Owners of dwellings with four or less apartments to install backflow
                                preventers on hose bibbs and shall warn them of the possible hazards of devices such as siphon type
                                pesticide or fertilizer sprayers, water operated sump pumps, etc. The Owner may be required to Install a
                                backflow preventer at the service entrance, If deemed necessary. (Note: This section does not exclude
                                the use of a single check valve at the service entrance.)

                        11.   A backfiow prevention device will be required on all projects, whereby the company is required to
                                remove and re-install a meter. This will include inside plumbing projects and renewal of service of existing
                                customers.

            B.     Owner's Responsibilities
                        1.     The Owner, after being Informed by a letter from the Supplier, shall at his expense Install, maintain and
                                test, or have tested, any backflow presenter on his premises.

                        2.     The Owner shall correct any malfunction of the backflow preventer which Is revealed by periodic testing.
                                This shall include the replacement of parts or the replacement of the backflow presenter if deemed
                                necessary by the Supplier.

                        3.     The Owner shall inform the Supplier of any new proposer or modified cross-connection and also any
                                existing cross-connection which the Owner is aware of but has not been found by the Supplier.

                        4.     Any Owner having a private well or other private water source must have a permit if the well or source is
                                cross-connected to the Supplier's system, and permission to cross-connect may be denied by the
                                Supplier. The Owner may be required to have a backflow preventer at the service entrance if a private
                                water source is maintained, even if it Is not cross-connected to the Supplier's system.

                        5.     The Owner shall not install a by-pass around any backflow preventer unless there is a backflow
                                prevented on the by-pass. Owners who cannot shut down operation for testing must supply the
                                additional devices necessary to allow testing to take place

                        6.     The Owner shall only install backflow preventers listed or approved by the Supplier and the Department.

                        7.     The Owner shall install the backflow preventer in a manner approved by the Supplier. Pit installations are
                                strongly discouraged and must have Department approval before a permit will be issued.

                        8.     If the Owner installs plumbing to provide potable water for domestic purposes which Is on the Supplier's
                                side of the backflow preventer, such plumbing must have its own backflow preventer.
VI. Degree of Hazard
            The Supplier recognizes the difference in the threat to the public water system arising from different types of
connection.  These can be classified as follows:

            A.     Class I - Low Degree of Hazard If backflow were to occur, the resulting health significance would be limited to
                    minor changes in the esthetic quality such as taste, odor or color. The foreign substance must be non-toxic and
                    non-bacterial in nature and have no significant health effect.

            B.     Class II - Moderate Degree of Hazard If backflow were to occur, the resulting effect on the water supply would
                    be significant changes In esthetic qualities. The foreign substance must be non-toxic to humans and non-bacterial
                      in nature.

            C.     Class III - High Degree of Hazard If backflow were to occur, the resulting effect on the water supply could
                    cause illness or death if consumed by humans. The foreign substance may be toxic to humans either chemically,
                    bacteriologically or radiologically. Toxicity may result from either short or long term exposure.
                        Class III hazards can be protected against by containment of fixture isolation.

                        1.     Examples of establishments which will be controlled by containment are:
                                    a.     Wastewater installations
                                                i.     Treatment plants
                                                ii.    Pump stations including storm water pump stations
                                                iii.   Industrial waste treatment plants
                                    b.     Industries where a health hazard exists.
                                    c.     Hospitals, nursing homes, clinics, etc.
                                    d.     Vessel watering points or fixtures.
                                    e.     Tank trucks, street sweepers, and other similar units which receive water at the Supplier's shop
                                            or any of its hydrants.

                        2.     Examples of establishments which the Supplier may cause to be controlled by either containment or
                                fixture isolation are:
                                    a.     Laboratories
                                    b.     Mortuaries or Funeral Homes
                                    c.     High pressure boilers \
                                    d.     Chemically treated low pressure boilers
                                    e.     Lawn irrigation systems
                                    f.      Swimming pools
                                    g.     Car wash facilities
                                    h.     Farms where water is used for other than domestic purposes
                                    i.      Commercial installations with very small industrial functions.
VII. Permits
            A.     Permits will be issued by the Department upon recommendation of the Supplier for any backflow situation
                    except those listed as exemptions in Section VIII, Part C.

            B.     Permits will only be issued if the cross-connection is deemed necessary and cannot be eliminated.

            C.     The degree of hazard will be stated on the permit.

            D.     The frequency of testing of the backflow presenter will stated of the permit.

            E.     The type, model and make of the backflow preventer will be listed on the permit. If more than one device Is
                    used to protect a single cross-connection, it shall be listed on the permit.

            F.     Any exemption will be listed on the permit. G. Permits shall be non-transferrable.

            H.     Permits shall be renewed every five years.

VII. Exemptions
            A.     Any cross-connection protected against backflow, at the time this program goes into effect, may continue with
                    that same protection unless:

                        1.     The existing protection is grossly inadequate.

                        2.     The Department notifies the Supplier, In writing, that a change must be made.

            B.     The exemption will be expired at any time the backflow presenter must be replaced and the replacement
                     backflow presenter must be that required by the degree of hazard involved.

            C.    Certain fixtures which constitute cross-connections may be controlled by non-testable backfiow preventers and
                    will not require a permit. Examples of these fixtures are as follows:

                        1.     Hose bibbs which are only potential cross-connections.

                        2.     Below the rim outlets which can be replaced by a gooseneck device.

                        3.     Toilets with anti-siphon ballcock.

                        4.     Any fixture with a built-in atmospheric vacuum breaker which cannot be bypassed.

                        5.     Others as listed in Appendix A of the State regulations.

IX. Periodic Testing
            It is recognized that any backflow preventer can fail and any method of protection can be subverted; thus, periodic
testing and inspection is necessary. This includes air gap protection.

            A.     Periodic testing shall be performed by the Owner and In the presence of either the Supplier or the Supplier's
                    agent.

            B.     The time interval for testing a backflow preventer be stated on the permit and shall be determined by the
                    Supplier.

            C.     Any backflow preventer which fails during test will be immediately repaired. The Supplier shall require that
                    repair parts be ordered within 24 hours and that shipment be by the fastest means possible. Any extended delay
                    (more than seven days) shall require discontinuance of service or other means to insure protection of the public
                    water system.

            D.     Certain Class III degree of hazard situations will not be allowed to continue unprotected if the backflow
                    preventer fails the test and cannot be immediately repaired. Owner will be the person responsible for the
                    provision of spare parts and should have a supply on hand.
 

MINIMUM REQUIREMENTS FOR CROSS CONNECTION PROTECTION
Building complex single owner
            2-4unit                             -                             dual check
            5-9 units                           -                             testable double checks
            10 or more units               -                             RPZ
Building complex multi owners
2-4 units                             -                             dual check
5 or more units                   -                             RPZ

Commercial preparation of food requires a testable double check.

Oil and gas service requires a testable double check.

Businesses that utilize petroleum products require a RPZ.

Funeral Homes require a RPZ.

Farm require a testable RPZ.

Schools require a testable double check.
 

REVISED 5/3/99
APPROVED BY TRUSTEES

HOME